• Reliable performance

    ADVANCE

    Downloads

    Leaflet
    Size:936.6 kB

    See all downloads

Videos

[trigger to render Video Gallery]

Images

Specifications Show all

General Information
ANSI Code
S62
Lamp type
70W HPS
Number of lamps
1 piece/unit
Circuit type
HX-HPF
Ballast type
Magnetic HID
Base model
71A7941
Core size
3 X 4 (2 coil)
Suitable for outdoor use
Yes
Ignitor catalogue number
LI551-H4
Ignitor temperature rating
105°C
Capacitor value
7 MFD
Capacitor catalogue number
7C070L30RA
Capacitor requirements
280V
Capacitor temperature rating
105°C
Capacitor diameter/oval dimensions
1.25 in
Capacitor height
2.75 in
Automatic restart
No
Operating and Electrical
Input voltage
480 V
Input frequency
60 Hz
Input current (open circuit)
0.36 A
Input current (starting)
0.21 A
Input current (short circuit)
0.15-0.25 A
Secondary short-circuit current
1.8-2.2 A
Constant wattage deviation
Within Trapezoid
Ballast factor (nom.)
1
Power factor (nom.)
0.90
Open circuit voltage
120 V
Input current (nom.)
0.21 A A
Input power (nom.)
93 W
Rated lamp power
70 W
Wiring
Wire strip length
0.5 mm
Wire length by colour
12"
Wire type
Stranded
Remote wiring configuration allowed
Yes
Max. ballast-lamp distance remote wiring
2'
Recommended fuse value
2 A
Approval and Application
Open circuit voltage test (volts)
110-130 V
Approval marks
ULR
CSA certificate
RoHS Compliant
Temperature marking
A
UL recognised
Yes
Hipot test (1 minute)
2000 V
Hipot test (2 seconds)
2500 V
UL insulation class
H(180°C)
UL temperature code
1029A
Product Data
Order product name
CORE & COIL HID 71A7941500D
EAN/UPC – product
781087794159
Numerator – quantity per pack
1
Numerator – packs per outer box
6
Material no. (12NC)
913700537909
Net weight (piece)
2.763 kg
Installation Diagrams
Downloads
Leaflets
Visuals
Brochures

Recently Viewed

  • Add product
     
  • Add product
     
  • Add product
     
Add product